5-216 L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS CHAPTER 5: SETTINGS
5
5.7 Grouped elements
5.7.1 Overview
Each protection element can be assigned up to six sets of settings with designations 1 to 6. The performance of these
elements is defined by the active setting group at a given time. Multiple setting groups allow the user to conveniently
change protection settings for different operating situations (for example, altered power system configuration or season of
the year). The active setting group can be preset or selected in the
SETTING GROUPS menu (see the Control Elements section
later in this chapter). See also the Introduction to Elements section at the beginning of this chapter.
5.7.2 Setting group 1
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6)
Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.31 or later to correct
this issue.
SETTING GROUP 1
LINE DIFFERENTIAL
ELEMENTS
See below
LINE PICKUP
See page 5-222
DISTANCE
See page 5-224
POWER SWING
DETECT
See page 5-245
LOAD ENCROACHMENT
See page 5-254
PHASE CURRENT
See page 5-255
NEUTRAL CURRENT
See page 5-267
WATTMETRIC
GROUND FAULT
See page 5-275
GROUND CURRENT
See page 5-279
NEGATIVE SEQUENCE
CURRENT
See page 5-286
BREAKER FAILURE
See page 5-292
VOLTAGE ELEMENTS
See page 5-302
SUPERVISING
ELEMENTS
See page 5-314
POWER
See page 5-321