5-142 L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
SYSTEM SETUP CHAPTER 5: SETTINGS
5
Figure 5-63: Example of use of sources
5.5.4 87L power system
5.5.4.1 Menu
SETTINGS  SYSTEM SETUP  87L POWER SYSTEM
Y LV D HV AUX
SRC 1 SRC 2 SRC 3
Phase CT M1 F1+F5 None
Ground CT M1 None None
Phase VT M5 None None
Aux VT None None U1
87L POWER SYSTEM
NUMBER OF TERMINALS:
2
Range: 2, 3
NUMBER OF CHANNELS:
1
Range: 1, 2
CHARGING CURRENT
COMPENSATN: Disabled
Range: Disabled, Enabled
POS SEQ CAPACITIVE
REACTANCE: 0.100 k
Range: 0.100 to 65.535 kin steps of 0.001