5-376 L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS CHAPTER 5: SETTINGS
5
5.8.12 Pilot schemes
5.8.12.1 Menu
SETTINGS CONTROL ELEMENTS PILOT SCHEMES
This menu is for selection and configuration of protection signaling schemes. All schemes are available for single-pole
tripping applications and can be used with one, two, or four-bit communications channels. Choices of communications
channel include Remote Inputs/Outputs and telecommunications interfaces.
For more information, see the Application of Settings chapter.
5.8.12.2 Direct under-reaching transfer trip (DUTT)
SETTINGS CONTROL ELEMENTS PILOT SCHEMES DUTT SCHEME
PILOT SCHEMES
DUTT SCHEME
See below
PUTT SCHEME
See page 5-378
POTT SCHEME
See page 5-380
POTT1 SCHEME
See page 5-383
HYBRID POTT SCHEME
See page 5-384
BLOCKING SCHEME
See page 5-388
BLOCKING1 SCHEME
See page 5-392
DCUB SCHEME
See page 5-393
DUTT SCHEME
DUTT SCHEME
FUNCTION: Disabled
Range: Disabled, Enabled
DUTT SCHEME BLOCK:
Off
Range: FlexLogic operand
DUTT SEAL-IN
DELAY: 0.010 s
Range: 0.000 to 65.535 s in steps of 0.001
DUTT NO OF COMM
BITS: 1
Range: 1, 2, or 4
DUTT RX1:
Off
Range: FlexLogic operand
DUTT RX2:
Off
Range: FlexLogic operand
DUTT RX3:
Off
Range: FlexLogic operand
DUTT RX4:
Off
Range: FlexLogic operand
DUTT SCHEME TARGET:
Self-Reset
Range: Self-Reset, Latched, Disabled
DUTT SCHEME EVENT:
Disabled
Range: Disabled, Enabled