ID3000/ID2000 Fire Panel Configuration Tool Manual
Control Matrix
4 - 24 997-291, Version 3.05
November 2010
Extinguishing System
a. Select one of the 32 available systems.
b. Use the ‘Activate Outputs Before Delay’
check box to select whether the output
action is to occur before (box checked) or
after (box unchecked) the delay configured
in the Control Matrix output statement.
‘Before Delay’ does not override the delay;
it allows an output to be activated before
the timer expires (e.g. use for warning
lamps, sounders, and the directional valve).
Use ‘After Delay’ for the releasing valve.
ab
CAUTION:
This product is not compliant
with EN 12094-1.
EN
12094-1
!
EN
12094-1
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
Evacuate, Reset, Silence, MCP in Walk
Test, TRUE
These options require no further definition,
except that Evacuate can be from Any panel
or a specific panel.
Remote Signal from Remote Fire Output
In VdS mode, digital input 2 can be configured to
provide a return signal from the remore fire signal
routing equipment. With the panel function set
to VdS mode activation of a fire alarm routing
equipment return signal drives this indicator.