997-291, Version 3.05
November 2010
ID3000/ID2000 Fire Panel Configuration Tool Manual
Panel Settings
2 - 15
1
2
3
2.8 Disablements Tab
This window sets various parameters
associated with disablements. Edit as follows:
1 If a remote switch is connected, or the Master
panel (Master/Slave Network) is required to
disable zones at a Slave, or the 3rd party
option is used, select what will be disabled
(sensors only, sensors and input modules,
or sensors, input and output modules).
Note: If a non-fire input is set to disable zones
in the Control Matrix (Section 4.3.2), the
devices that will be disabled are those
selected in step 1.
2 Check this box if the panel’s common
DISABLEMENT LED is not to illuminate
when the DELAYS ACTIVE LED is lit.
Note: The default configuration is that a delay
active does not illuminate the common
disablement LED. EN54-2 : A1:2006
removes the requirement that a delay
should be indicated as a disablement.
Select as appropriate in accordance with
local fire regulations.
3 Only available when ‘VdS’ mode is set on the
Specification Tab. If this box is checked, the
function of the panel’s Silence/Resound
pushbutton (Akustik AB-/Anstellen) becomes
Disable/Enable (Akustik AB/AN). The latter
is not EN54-compliant, so leave the box
unchecked unless the pushbutton’s label as
supplied with the panel is ‘Akustik AB/AN’.
EN54-2: 7.8
The ‘Silence/Resound’ control is
required.