ID3000/ID2000 Fire Panel Configuration Tool Manual
Panel Settings
2 - 4 997-291, Version 3.05
November 2010
2.2 Loop Setting Tab
Set the number of loops to that present on your
panel.
Edit as follows:
1 Check the Loops 3-4 fitted, Loops 5-6 fitted,
and Loops 7-8 fitted boxes as appropriate
to your panel. ID3000 only: For each pair of
loops fitted, select the appropriate Type of
LIB, either Standard LIB or E(nhanced)LIB.
The total Number of Loops is displayed
automatically (if no boxes are checked, the
total is 2, i.e. those on the Base PCB).
Note: ELIBs must be used if there are more
than 512 monitored points on the system.
Selecting the ELIB Type on the Tool
means that the panel will indicate a fault
if ordinary LIBs are fitted. This is used to
confirm compliance with EN54. No fault
is indicated if Standard LIB is selected
but ELIBs are fitted.
1
EN54-2: 13.7
Maximum of 512 Sensors and/
or MCPs per panel unless
ELIBs are used