ID3000/ID2000 Fire Panel Configuration Tool Manual
Panel Settings
2 - 24
2.12 Alarm Coincidence Tab
Allows multiple zone or device coincidence to
be configured at the input of a Control Matrix
entry. Edit as follows:
1 For each Zones level (where ‘level’
indicates the position on the panel’s Control
Matrix ‘Multiple Zone Coincidence Rule’
menu), enter the number of zones that
must be in alarm at the Control Matrix input.
2 For each Devices level (where ‘level’
indicates the position on the panel’s Control
Matrix ‘Select Coincidence Rule’ menu),
enter the number of devices that must be
in alarm at the Control Matrix input.
The configured values then become available
for selection for the Control Matrix Input Event
(Section 4.3.1).
3 Select the scope of device coincidence
when the Control Matrix input zone
selection is ANY ZONE:
a. The devices must be on the same panel,
or (networked panels) on any panel of the
network. This is the default.
b. The devices must be in the same zone.
4 Select the scope of device coincidence in
cells:
a. Two or more devices in alarm in the same
cell. This is the default.
b. Two or more devices in alarm within the
selected range of cells.
3
1
2 4