ID3000/ID2000 Fire Panel Configuration Tool Manual
Panel Settings
2 - 12
2.6 Remote Fire Outputs Tab
These settings allow each of the four internal
sounder/relay circuits and the Fire VFCO
Relay to be configured in software as remote
fire outputs (i.e. outputs that are subject to the
Day Mode two-stage investigation time, see
Section 2.9). Edit as follows:
1 Set each Output Circuit and the relay to
the required function. Output Circuits 3 &
4 are only available when any selectable
option other than VdS mode is set on the
Specification Tab. In VdS mode, to
configure a ÜE set Circuit 1 or 2 to Remote
Fire Output and configure a hardware link.
If the Fire VFCO Relay is set to Remote
Fire Output then its operation follows that
of the ÜE with respect to delayed mode,
disablement etc.
Note: If Output Circuit 3 or 4 is set to Sounder/
Relay, then the Sounder or Relay
function is determined by a hardware
link. Links are described in the panel’s
Installation and Commissioning Manual.
2 Optional: if any Voice Outputs have been
configured, select one sounder/relay circuit
as backup.
1 2