ID3000/ID2000 Fire Panel Configuration Tool Manual
Panel Settings
2 - 11 997-291, Version 3.05
November 2010
8
6 Set to either STEADY or PULSE according
to the type of signal returned by the ÜE.
PULSE avoids the panel reporting a fire if
the ÜE return signal appears to reset while
the panel is in alarm.
7 Set normal activation pulse length (range 1
to 60 seconds, or 0 for continuous)
dependent upon the type of ÜE connected.
8 Set test pulse length (range 1 to 60 seconds).
This is the minimum time the ÜE is activated
when the FBF’s ÜE Test pushbutton is
pressed (may may be extended by holding
in that pushbutton).
9 Select the method used by the panel to
interface to the extinguishing system (SST).
The default setting is ‘VdS 2540 with 2
inputs’.