ID3000/ID2000 Fire Panel Configuration Tool Manual
Panel Settings
2 - 18
2.9 Day/Night Mode Tab
This tab is only available if a remote fire output
has been configured. For VdS, also ensure that
a ÜE is configured in the panel hardware. This
tab allows configuration of a two-stage
investigation time which delays activation of
the fire output(s)/ÜE (does not delay
sounders). Edit as follows:
1 Use the spin buttons to set the first-stage
time, range 0 to 120 seconds. This time is
initiated by an alarm if Day Mode is set
active (by the panel’s DAY MODE
pushbutton or by a remote switch).
2 Use the spin buttons to set the second-stage
investigation time, range 1 to 10 minutes.
This time is initiated when the panel’s
EXTEND DELAY pushutton is pressed while
the first-stage time is active; it replaces (is
not added to) the first stage time.
3 Select whether or not the delay is cancelled
if there is a new alarm during the second
investigation period (box is checked by
default).
4 Select whether type SPRINKLER acts in
the same way as type MCP (box is left
unchecked by default).
5 Select whether a change of state at Input 2
of the panel results in a change from Day
Mode to Night Mode, or Day/Night in either
direction, or has no effect.
1 2 3
45