ID3000/ID2000 Fire Panel Configuration Tool Manual
Panel Settings
2 - 22
8 ID2000 only: If set the total number of
devices indicating a fire is shown on the
top line of the panel’s LCD, otherwise it is
not shown.
9 If a device indicates an alarm and then the
alarm condition is removed, then by default
its LEDs pulse. If it is required that the LEDs
remain on then select the ‘Steady’ option.
10 After SILENCE SOUNDERS has been
actioned sounder operation can be
configured to: always respond to a new
alarm; respond to a new alarm in a zone
not already in alarm; respond to a second
alarm in a zone already in alarm; or never
to respond. The re-sound default is
‘Always’.
11 This option must only be used in
consultation with appropriate technical
guidance. This function has now been
superseded by the configurable option
described above (item 10).
ID3000
9
ID2000
10
11 8