ID3000/ID2000 Fire Panel Configuration Tool Manual
Control Matrix
4 - 19 997-291, Version 3.05
November 2010
2a
2b
2c
2 Specify Zone(s) or Cell(s), dependent upon
the event chosen in step 1. Also allows
Zone Coincidence to be set. Possible
options are:
a. Any zone. The options are for the input
alarm to be from a single zone only, or from
the number of alarms selected in the drop-
down list*.
b. Specific Zone(s). Allows the zone number
or range (maximum difference of 32) to
be selected. Also allows the number of
zones that must be in coincident alarm to
be set as in (a) above (if box is unchecked
there is no coincidence).
c. Specific Cell(s). Maximum range is 32.
Note: *The available numbers of zones or
devices are ‘2’ plus those configured on
the Alarm Coincidence tab
(Section 2.12). Zone coincidence is
only available for the input event type
‘Alarm’ and when Any zone or a range
of zones is specified.
Multiple zone coincidence: for the
Control Matrix entry to be valid, the
number of coincident zones must not
exceed the chosen zone range.