EasyManuals Logo
Home>Honeywell>Control Panel>Notifier ID3000

Honeywell Notifier ID3000 User Manual

Honeywell Notifier ID3000
147 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #99 background imageLoading...
Page #99 background image
ID3000/ID2000 Fire Panel Configuration Tool Manual
Control Matrix
4 - 22 997-291, Version 3.05
November 2010
Pre-Alarm
The options are similar to those available for
Alarm, however:
a. Zone coincidence is not available.
b. Device coincidence is only available for
two devices.
Fault
Select the source of the fault:
a. Any zone, which includes PSU, panel and
system faults that are not attributable to a
zone.
b. A specified zone or range of zones (there
is no coincidence option).
c. General Panel Fault, which selects any
fault as the input.
d. Virtual Input Point (future development).
Disablement
Select the source of the disablement:
a. Any zone.
b. A specified zone or range of zones (there
is no coincidence option).
c. General (any input or output that causes
the panel’s DISABLEMENT indicator to
light).
d. A sounder circuit or remote fire output.
e. Virtual Input Point (future development).

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier ID3000 and is the answer not in the manual?

Honeywell Notifier ID3000 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier ID3000
CategoryControl Panel
LanguageEnglish