EasyManuals Logo
Home>IDEC>Controller>FT1A Series

IDEC FT1A Series User Manual

IDEC FT1A Series
393 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #252 background imageLoading...
Page #252 background image
10: U
SER
C
OMMUNICATION
I
NSTRUCTIONS
10-16 S
MART
AXIS P
RO
/L
ITE
U
SER
'
S
M
ANUAL
FT9Y-B1378
User Communication Client
When a client connection is configured as the user communication client, the SmartAXIS communicates with the specified server
device according to the settings configured in the ETXD and ERXD instructions that are programmed for the client connection. The
remote host number and other communication settings can be configured in the Connection Settings tab in the Function Area
Settings dialog box.
Specifications (User Communication Client)
Note 1: Can be enabled or disabled in Function Area Settings, Connection Settings.
Note 2: The settings can be configured in the Connection Settings tab in the Function Area Settings dialog box.
Note 3: The receive timeout is enabled when using the ERXD instruction. To disable the receive timeout, set it to 25500 ms.
Establishing/Disconnecting User Communication Client Connections
When user communication clients are configured, connections are established on TCP/IP protocol. The connections are established
when ETXD/ERXD instructions are executed or when the SmartAXIS has started to run (See Note 1 above). After a connection has
been established, the connection will be kept open until either the SmartAXIS is stopped or a special internal relay allocated to the
connection is turned on.
User Communication Client Receive Instruction (ERXD) Cancel Flag
The allocation of the user communication receive instruction cancel flags for each client connection is shown in the table below.
For details about the user communication receive instruction cancel flag, see Chapter 25 "User Communication Instructions" in the
SmartAXIS Ladder Programming Manual.
Item User Communication Client
Remote host number 1 to 255
Establish connection
When ETXD/ERXD Instructions are executed
When the SmartAXIS starts to run (Note 1)
Disconnect connection
When the SmartAXIS is stopped
When special internal relays (M8130 to M8132) are turned on
Number of remote hosts that the SmartAXIS
can communicate simultaneously
One remote host per a user communication client (Note 2)
Receive timeout 100 to 25400 ms (100 ms increments); Default: 1000 ms (Note 3)
Device Address Description Operation
M8130 Connection 1 Disconnect
When the reply is turned on, the corresponding
connection is disconnected.
M8131 Connection 2 Disconnect
M8132 Connection 3 Disconnect
Device Address Description
M8100 User Communication Receive Instruction Cancel Flag (Connection 1)
M8101 User Communication Receive Instruction Cancel Flag (Connection 2)
M8102 User Communication Receive Instruction Cancel Flag (Connection 3)