S
MART
AXIS P
RO
/L
ITE
U
SER
'
S
M
ANUAL
FT9Y-B1378 2-23
2: P
RODUCT
S
PECIFICATIONS
Communication Cartridge
Functions
By installing a communication cartridge on the SmartAXIS expansion communication port, the SmartAXIS can communicate with
communication devices supporting RS232C/RS485, such as Modbus RTU compliant devices, barcode readers, or operator
interfaces.
Specifications
Note: For details on recommended communication cables, see "Cables" on page A-8.
Installation Procedure
Remove the expansion communication port cover by inserting a flat head screwdriver into the slots at the top and bottom of the
cover. Press in the tabs at either end of the cover and lift the cover directly upward.
Type No. Item Specifications
FT1A-PC1
Termination Connector Mini DIN
Standards EIA RS232C
Maximum Baud Rate 115,200 bps
Communication Functions Maintenance communication, User communication, Modbus RTU master/slave
Isolation between Internal Circuit
and Communication Port
Not isolated
Recommended Communication Cable Special cable
FT1A-PC2
Termination Connector Mini DIN
Standards EIA RS485
Maximum Baud Rate 115,200bps
Communication Functions Maintenance communication, User communication, Modbus RTU master/slave
Isolation between Internal Circuit
and Communication Port
Not isolated
Recommended Communication Cable Special cable
FT1A-PC3
Termination Connector Screw Terminal block
Standards EIA RS485
Maximum Baud Rate 115,200 bps
Communication Functions Maintenance communication, User communication, Modbus RTU master/slave
Isolation between Internal Circuit
and Communication Port
Not isolated
Recommended Communication Cable
Twisted-pair shielded cable with a minimum core wire of 0.3 mm
2
(Conductor resistance 85 /km maximum, shield resistance 20 /km maximum)
Maximum Cable Length 200m
Expansion Communication Port Cover
Slot
Flat Head Screwdriver