103
5 Functional Description with Process Diagrams
5.4 Burner Firing Rate Controller
5.4.1 Requirements
NOTICE
Purchase option: This function must be purchased and mapped.
5.4.2 Required Inputs/Outputs
The actual value is assigned to the analogue input in the IO-Matrix dialogue of the CMS Re-
mote Software.
The setpoint values can be switched by means of the digital input signal ’PLC firing rate con-
troller input setpoint changeover’.
• Input HIGH: setpoint 1
• Input LOW: setpoint 2
5.4.3 Required Parameters
5.4.3.1 Configuration
Activate or deactivate the firing rate in P0040.
Set the PID settings in P0057, P0058 and P0059.
P no. Description Attributes
40 Operating mode of the firing-rate controller (0-OFF; 1-constant control; 2-controlled by
atmospheric conditions)
V1.0.0.0
Operating mode of the firing-rate controller
0 = OFF
1 = constant control
2 = controlled by atmospheric conditions
Write: 1/GUI/UI
Read: 0
Default: 0
Min: 0
Max: 2
57 P Term V1.0.0.0
Proportional term of the controller. Write: 0/GUI/UI
Read: 0
Default: 3
Min: 0
Max: 65535
58 I Term V1.0.0.0
Integral term of the controller Write: 0/GUI/UI
Read: 0
Default: 60
Min: 0
Max:999
59 D Term V1.0.0.0
Derivative term of the controller Write: 0/GUI/UI
Read: 0
Default: 10
Min: 0
Max: 65535