8.9.3 Password Entry
Information regarding password entry for the connected devices can be found in the corre-
sponding basic documents in Chapter 1.1 Validity of these Instructions.
Information regarding password entry with UI400 see chapter 7.1.5.1 Password
Information regarding password entry with GUI60x see chapter 7.2.2 Password
Information regarding password entry with CMS Remote Software see chapter 7.3.3.3 Access
Rights Menu
8.10 Installation and Commissioning
8.10.1 Guidelines for Commissioning CO/O2 Controller
Commissioning of the CO/O
2
control
1. Check terminal resistances on LT and the devices connected to the LSB
and reset if necessary.
2. Activate CO/O
2
control on CMS.
8.10.8 Commissioning the CO/O2 Control
alternatively by UI400 (8.10.8.1 Commissioning with UI400) or CMS Remote Software
(8.10.8.2 Operating with PC Remote Software)
3. Compare the CO/O
2
measurement device (LT3-F) offset (air) and operating point.
See basic document LT3-F: Offset calibration (publication no. DLT3140)
See basic document LT3-F: O
2
calibration (publication no. DLT3140)
See basic document LT3-F: CO
e
calibration (publication no. DLT3140)
4. Check or enter O
2
setpoint curve on CMS
Entering the O2 Setpoint Curve
NOTICE
No CO control without an O
2
setpoint curve!
*******
5. Set correctional range on CMS.
Recommendation for CO control:
Speed ï‚® 300
Air damper ï‚® 100
Recommendation for O
2
trim:
Speed ï‚® 150
Air damper ï‚® 50
*******
The O
2
setpoint curve is only regarded as present when there are at least 3 pro-
grammed O
2
setpoint values.