EasyManuals Logo
Home>Lamtec>Control Systems>UI400

Lamtec UI400 User Manual

Lamtec UI400
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
68
4 CMS Components
Allocation between Function and Bits see Parameter list DLT7202.
4.6.7 Interfaces
Failsafe communication via iLSB.
Type of
Input
Configuration Software Configuration Software
Sensors Connection Parameter IO-Matrix
Non-fail-
safe
1 per input = 1 nsi
signal
see Fig. 4-29 SAI connection dia-
gram
P 1270
Bit 0 ... 6: Function
Bit 7 = 0
Mapping as nsi AI
Failsafe,
linked
1 per 2 inputs =
1 si signal
see 4.6.6 Connection Diagram
Switch in parallel pairs IN+ and IN-
(Pin 2 and 3)
– Input 1 to 2
– Input 3 to 4
– Input 5 to 6
– Pt100/Pt1000:
Ref+ (PIN1) additional in parallel
P 1270
Bit 0 ... 6: Function
Bit 7 = 1
Mapping as si AI
Failsafe,
not linked
2 per 2 input = 1 si
signal
see Fig. 4-29 SAI connection dia-
gram
Sensor connections are independ-
ent to each other
P 1270
Bit 0 ... 6: Function
Bit 7 = 0
Mapping as si AI