129
7 Operating Control and Displays
7.1.5.4 Setting Curves
How to set the servomotors curve sets
NOTICE
The servomotors are running to the new position immediately after the modification.
To adjust channel 4 the fan motor must be running. The feedback setpoint curve of channel 4
must rise continuously.
NOTICE
The following firing rate points are available:
Ignition point , 200, 250, 300, 400, 500, 600, 700, 800, 900, 999
... Firing rate point - from ignition position up to 999
S
I
X
Setpoint value channels 1 ... 3
Actual value channels 1 ... 3
(in this case: channel 1 = oil, channel 2 = air channel
3 = OFF)
Curve data for this firing rate point are stored yet
Pressing key BACK for longer than 2 s in menu ’Curve settings of the servomotor
causes a fault shut down.
Pressing key BACK after finishing the curve settings leads back to menu ’ Settings’.
Pressing key BACK during changing the firing rate discards the modification.