43
4 CMS Components
4.2.8 Approved Actuators
Further servo motors are in the pipeline.
4.3 AEC-VS – Actuator Extension Component Variable Speed
Extension Module for Frequency Inverters
4.3.1 For Your Safety
When using the module to provide speed feedback for a frequency-controlled fan, it must
be ensured that values cannot exceed or drop below the selected measurement range.
Check the parameter settings!
For motors with 0/4 - 20 mA position preset, the position feedback must be independent
of and non-interacting with the preset.
When using a frequency controlled fan, the actual speed of the fan must be used as feed-
back - either by connecting the speed sensor directly to the AEC-VS or by interconnecting
a converter to 4 ... 20 mA
A 4 ... 20 mA feedback signal that comes directly from the FI or a signal that does not
directly represent the fan speed is invalid must not be processed.
The digital input 1 and the digital output of the AEC-VS must not be used for safety-rele-
vant functions.
DANGER!
Warning! Risk of short circuit and electric shock!
Incorrect wiring can lead to a short circuit and irreversible damage to the connected equipment
or may cause an electric shock.
For connections with SELV, always ensure a safe isolation from the supply voltage in the
wiring and with the connected equipment!
662R2127 6 Nm
662R2111 20 Nm
662R2121 40 Nm
662R2123 90 Nm
662R2125 180 Nm
668M2006 6 Nm
668M2020 20 Nm
668M2040 40 Nm