48
4 CMS Components
4.3.4 Functional Description
The AEC-VS is equipped with:
• Pulse input for connecting inductive proximity sensors with NAMUR interface
• Pulse input for connecting inductive proximity sensors with 3-wire interface
• Analogue input for the connection of rotary encoders with current interface 0/4 - 20 mA or
position indicators from actuator drives with current interface 0/4 - 20 mA
• Non-failsafe, digital output (typically configured for ’Fan ON’)
• Analogue current output 0/4 - 20 mA
• Analogue voltage output 2/0 - 10 V
• Non-failsafe, digital input (typically configured with ’Fan fault’)
Channel configuration
Parameters are scaling the channel feedback.
• AEC-VS configuration lower range (P 48, P 50)
• AEC-VS configuration upper range (P 49, P 51)
The type of the used input must be set in ’AEC-VS configuration input’.
Setting the parameters require a reboot of the system.
4.3.5 LEDs
LED Col-
our
Explanation
PWR Gree
n
LED is active as soon as the device is supplied with voltage.
Burner firing-rate In operation
ERR – ON: There is a fault
– Flashing at 2 Hz:
Device initialising
– ON: There is a fault.
– OFF: No fault
iLSB Yel-
low
– Flashing at 2 Hz:
iLSB initialising
– Permanent light:
iLSB successfully initialised
– OFF and ERR-LED OFF:
Passive mode
*
– OFF and ERR-LED ON:
Fault during system layer
initialisation
– Permanent light: iLSB communication OK,
Module is in operation
– Short flashing (60 ms on/140 ms off):
Synchronisation
– Short flashing (140 ms on/60 ms off): IDLE
– Short flashing (50 ms on/50 ms off):
Middleware fault
S1 Yel-
low
– Flashing at 2 Hz:
EEPROM initialising
– Permanent light:
EEPROM successfully
initialised
– OFF: There are no indications/messages from the
middleware.
– ON: There are indications/messages from the
middleware