EasyManuals Logo
Home>Lamtec>Control Systems>UI400

Lamtec UI400 User Manual

Lamtec UI400
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #67 background imageLoading...
Page #67 background image
66
4 CMS Components
SAI terminal assignment
Connection examples
Pulses – NAMUR Pulses – 3-wire Pot Pt100/Pt1000 0 … 10 V 0 … 20 mA
+24 VDC from MCC (e.g. X33 pin 2/4)
Pin 1 Ref+
SAI X11–X16
Pin 2 In+
Pin 3 In-
Pin 4 GND
Fig. 4-30 0 … 10 V signal transmitter (here: pressure transmitter)
+24 VDC
Pin 1 Ref
SAI X11–X16
Pin 2 In+
Pin 3 In-
Pin 4 GND
Fig. 4-31 0/4 … 20 mA signal transmitter, 3-wire
(here: pressure transmitter)