5-2
LD,LDI,AND,ANI,OR,ORI
5.1 Contact Instructions
5.1.1 Operation start, series connection, parallel connection
(LD,LDI,AND,ANI,OR,ORI)
LD,LDI,AND,ANI, OR,ORI
Function
LD, LDI
(1) LD is the A contact operation start instruction, and LDI is the B contact operation start
instruction. They read ON/OFF information from the designated device*
1
, and use that as an
operation result.
*1: When a bit designation is made for a word device, the device turns ON or OFF depending on the 1/0 status of
the designated bit.
: Devices used as contacts (bits)
Setting
Data
Internal Devices
R, ZR
J\
U\G
Zn Constants
Other
DX, BL
Bit Word Bit Word
––
Basic
Process
High
performance
Redundant
Universal
LCPU
X1/D0.1
X1/D0.1
Bit device number / Word device bit designation ( )
X2/D0.2
X2/D0.2
X3/D0.3
X3/D0.3
S
LD
LDI
AND
ANI
OR
ORI
S
S

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals