5-11
OPERATION
Adjustment level
No key operation for 10
seconds at the adjustment
level causes the product to
return to the current value
display mode at the operation
level automatically.
5-8 Specifying the Temperature Input Correction Value (K3MA-L)
5-8 Specifying the Temperature Input
Correction Value
(K3MA-L)
This parameter allows you to set a correction value for temperature input.
The input temperature is corrected by the quantity of set value in the whole of sensor
range.
If the correction value is 1.2°C, the current value of 200°C before correction will be
processed as 201.2°C after correction.
Procedure
A. Press the L key at the operation level to move
to the adjustment level.
•"
a
" will appear on the level indicator, indicating
the product has entered the adjustment level.
B. Press the S key to display the set value of the
parameter on the main indicator.
• The current set value for temperature input cor-
rection value will appear on the main indicator.
C. Press the S key again.
• The set value will start blinking, indicating the
product is in the change state.
D. Use the S and U keys to change the set value.
E. Press the M key to save the change.
• The change is saved and then the main indicator
returns to the parameter display mode.
F. Press the L key to return to the operation level.
Parameter Set value
Description
in5 :999-9999
-1999-9999: Temperature input correction
value