6-4 Average Processing
This function averages a specified number of measurements.
It is useful for preventing readout from fluctuating due to unstable input such as spike
noise.
The average processing of the K3MA provides a simple average (an arithmetic mean).
The number of measurements for averaging that can be specified is as follows.
- No average processing (the number of measurements for averaging: 1)
-2
-4
-8
The number of measurements for averaging is the number of times the process value
is updated as described in "Measurement".
The following shows the relationship between the number of measurements for
averaging and the interval at which the process value and comparative output are
updated.
Number of
measurements
for averaging
Update interval
K3MA-J K3MA-L
K3MA-F
Input pulse
4 Hz and more
Input pulse
Less than 4 Hz
No average
processing
250 ms 500 ms 250 ms Every input pulse
2 500 ms 1 second 500 ms
Every 2 input
pulses
4 1 second 2 seconds 1 second
Every 4 input
pulses
8 2 seconds 4 seconds 2 seconds
Every 8 input
pulses