5-30
OPERATION
Advanced-function setting level
CHAPTER 5 OPERATION
5-21 Specifying the Start-up
Compensation Time
(K3MA-F)
This parameter allows you to specify the start-up compensation time.
The start-up compensation time is a delay between power-on of the product and the
start of measurement. This function is useful in preventing output from being
produced until a rotator reaches a prescribed speed.
Procedure
A. When the product is at the operation level, press
the L key and hold it down for at least three
seconds to enter the initial setting level.
•"
5
" will appear on the level indicator, indicating
the product has entered the initial setting level.
B.
Enter password "-0169" in parameter "
amov
" to
enter the advanced-function setting level. For
details on how to move to the advanced-function
setting level, refer to "5-2 Moving among Levels".
•"
f
" will appear on the level indicator, indicating
the product has entered the advanced-function
setting level.
C. Press the M key several times until parameter
"s-tmr" appears on the main indicator.
D. Press the S key to display the set value of the
parameter on the main indicator.
• The current set value of the start-up compensa-
tion timer will appear on the main indicator.
E. Press the S key again.
• The set value will start blinking, indicating the
product is in the change state.
F. Use the S and U keys to change the set value.
G. Press the M key to go to the next parameter.
• The change is saved.
H. Press the L key and hold it down for at least
one second to return to the initial setting level.
I. Press the L key and hold it down for at least
one second to return to the operation level.
Parameter Set value
Description
s-tmr 0.0-99.9 0.0 to 99.9 seconds: start-up compensation time