Final Configuration
4-16 StorageTek SL150 Modular Tape Library Installation Manual
Reset the Library with Manufacturing Default Values
To reset the library with manufacturing default values:
1. Push and release one of the Locate buttons on the library to enable the Locate
indicators.
The Locate button is in the upper left corner of the front control panel or at the rear
of the library on the robot CRU in the black Library section (see "Library
Indicators").
2. Simultaneously press and hold both the front and rear Locate buttons for
approximately 10 seconds.
Holding both buttons is more easily accomplished by using two people.
3. Wait for the Locate indicator to flash at a fast rate before releasing the Locate
buttons.
The library is reset to manufacturing default values.
4. Press the library power switch if the library does not restart.
5. Repeat the library initialization steps and apply the changes.
Note: Refer to the Oracle Key Manager documentation if you
intend to enable tape drive encryption for HP LTO drives.
Note: After approximately four seconds, the indicator flashes at a
slow rate.
Note: If either Locate button is released before the fast flash rate,
the reset process terminates.