104 Rockwell Automation Publication 2715P-UM001C-EN-P - March 2019
Chapter 7 Troubleshooting
To restore the terminal to its default state, follow these steps.
1. Cycle power to the terminal.
The Allen-Bradley® logo displays during startup.
2. Wait a few seconds, and then touch the Allen-Bradley logo when th
e
cop
yright line becomes brighter.
The normal startup is suspended so the restore procedure can initiate.
You are asked if you want to restore the terminal to its defaults.
3. To continue tap Yes, or tap Cancel to resume a normal startup.
You are asked to confirm the removal of all user files such as applications.
4. To continue tap Yes, or tap Cancel to resume a normal startup.
Progress messages appear on the screen during the restore operation.
When the restore is complete, the terminal performs a normal startup.
5. From the Settings menu, update the terminal network settings.
6. Download an application to the terminal by using the View Designer
application.
7. From the Settings menu, update any remaining terminal settings as
appropriate.
For details on how to modify device configuration settings, see Disable
Downloads to the Terminal on page 58.
Dispose of the Terminal
These terminals contain heavy metals that can contaminate the earth. Therefore,
check with local health and sanitation agencies for ways to dispose this
equipment safely.
TIP Wait a few seconds before you touch the logo. If you touch the logo
too soon during startup, this error text is displayed under the
copyright line.
ERROR! FEHLER! ERREUR! ERRORE!
If this error text is displayed, cycle power to the terminal and wait a
few seconds longer before you touch the logo.
At the end of its life, collect the terminal separately from any unsorted municipal
waste.