82 Rockwell Automation Publication 2715P-UM001C-EN-P - March 2019
Chapter 5 Install and Replace Components
2. Insert the SD card firmly into the slot
u
ntil you hear a click.
When you hear the click, the card ha
s
lo
cked into pl
ace.
T
o remove the card, push the card in
slightly to unlock the SD card so you ca
n
r
emove it from the slot.
Replace the Battery
The product has a lithium battery that provides back-up power for the real-time
clock. The battery can be replaced while the product is mounted in the panel.
You need a #1 Phillips screwdriver (#1 Phillips bit) to remove the logic module
and access the battery.
Perchlorate material – special handling apply. See www.dtsc.ca.gov/
hazardouswaste/perchlorate.
This perchlorate warning only applies to primary Lithium Manganese Dioxide
(LiMnO
2
) cells or batteries, and products containing these cells or batteries, sold
or distributed in California, USA.
ATTENTION: Orient the SD card correctly before you insert it into the slot. If
you force the card into the slot, you can damage the card or the terminal.
1
6
1
6
SD Slot
This product contains a sealed lithium battery, which need to be replaced during
the life of the product.
At the end of its life, the battery contained in this product should be collected
separately from any unsorted municipal waste.
The collection and recycling of batteries helps protect the environment and
contributes to the conservation of natural resources as valuable materials are
recovered.
WARNING: There is a danger of explosion if the lithium battery in this product
is incorrectly replaced. Do not replace the battery unless power has been
removed and the area is known to be nonhazardous.
Replace the battery only with catalog number 2711P-RY2032 or an equivalent
CR2032 coin-cell battery.
Do not dispose of the lithium battery in a fire or incinerator. Dispose of used
batteries in accordance with local regulations.
For safety information on the handling of lithium batteries, including handling and
disposal of leaking batteries, see Guidelines for Handling Lithium Batteries,
publication AG 5-4
.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PanelView 5510 Series and is the answer not in the manual?

Rockwell Automation Allen-Bradley PanelView 5510 Series Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PanelView 5510 Series
CategoryTouch terminals
LanguageEnglish

Related product manuals