191
LOGO! Manual
A5E00067781 01
LOGO! 230RCL
LOGO! 230RCLB11
LOGO! 230RC
LOGO! 230RCo
Delay time at
0 after 1 Typically 50 ms Typically 50 ms
1 after 0
Typically 50 ms
Typically 50 ms
Line length (unshielded) 100 m 100 m
Digital outputs
Number 4 8
Output type Relay outputs Relay outputs
Electrical isolation Yes Yes
In groups of 1 2
Activation of digital input Yes Yes
Continuous current I
th
(per
connector)
Max. 10 A Max. 10 A
Incandescent lamp load
(25,000 switching cycles) at
230/240 V AC
115/120 V AC
1000 W
500 W
1000 W
500 W
Fluorescent tubes with electr.
control gear (25,000 switch-
ing cycles)
10 x 58 W (at
230/240 V AC)
10 x 58 W (at
230/240 V AC)
Fluorescent tubes, conven-
tionally compensated (25,000
switching cycles)
1 x 58 W (at
230/240 V AC)
1 x 58 W (at
230/240 V AC)
Fluorescent tubes, uncom-
pensated (25,000 switching
cycles)
10 x 58 W (at
230/240 V AC)
10 x 58 W (at
230/240 V AC)
Short circuit–proof cos 1 Power protection
B16
600A
Power protection
B16
600A
Short–circuit proof cos 0.5 to
0.7
Power protection
B16
900A
Power protection
B16
900A
Technical Specifications