4.4.10 Twelve-Month Time Switch
Brief description
The output is controlled by a definable on/off date.
Symbol in
LOGO!
Connection Description
Input No Use the No parameter to set
the on and off times for the
cam of the twelve-month
time switch.
Output Q Q switches on when the
parameterizable cam is
switched on.
Timing diagram
MM.DD+
On=02.20
Off=04.03
On
Off
February 20 April 3
Feb.
Mar. Apr.
Description of function
At the on time, the twelve-month time switch switches the
output on and at the off time, it switches the output off. The
off date indicates the date on which the output is reset to 0.
The first value indicates the month, the second value indi-
cates the day.