4.4.13 Symmetrical Clock Pulse Generator
Brief description
A clock pulse with a definable period length is output at the
output.
Symbol in
LOGO!
Connection Description
Input En The En input switches the
clock pulse generator on
and off.
Parameter T T is the time for which the
output is switched on or off.
Output Q Q switches on and off cycli-
cally in time with the pulse
period T.
Parameter T
Please refer to the note in Section 4.3.2 when specifying
the values.
Timing diagram
En
Q
T T
T T
The bold part of the timing diagram appears in the symmetrical
clock pulse generator symbol.
Description of function
The parameter T specifies the length of the on and off peri-
ods. Use the En (enable) input to switch the clock pulse
generator on. The pulse generator sets the output to 1 for
the time T, then to 0 for the time T and so on until the En
input is a 0.