4. During the test run, check and document the following:
Check whether it is running smoothly.
Document the voltage, current and power values. As far as possible, document the
corresponding values of the driven machine.
If this is possible using the available measuring equipment, check the bearing and stator
winding temperatures until they have reached steady-state values.
Check the machine for noise or vibrations on the bearings or bearing shields as it runs.
5. In case of uneven running or abnormal noise, switch off the machine. As the machine runs
down, identify the cause.
If the mechanical operation improves immediately after the machine is switched off, then
the cause is magnetic or electrical.
If the mechanical running does not improve immediately after switching the machine off,
then the cause is mechanical.
- Imbalance of the electrical machine or the driven machine
- The machine set has not been adequately aligned
- The machine is being operated at the system resonance point. System = motor, base
frame, foundation, ...
NOTICE
Serious damage to the machine
If the vibration values in operation are not maintained in accordance with DIN ISO
10816-3, then the machine can be mechanically destroyed.
During operation, observe the vibration values in accordance with DIN ISO 10816‑3.
NOTICE
No-load operation without cantilever force
Never operate motors with cylindrical roller bearings in no-load operation without any
cantilever force Otherwise, this could damage the bearings.
7.7 Set values for monitoring the bearing temperature (optional)
Prior to commissioning
If the machine is equipped with bearing thermometers, set the temperature value for
disconnection on the monitoring equipment before the first machine run.
Table 7-1 Set values for monitoring the bearing temperatures before commissioning
Set value Temperature
Alarm 115 °C
Shutting down 120 °C
Commissioning
7.7 Set values for monitoring the bearing temperature (optional)
SIMOTICS M-1PH8 1PH818., 1PH822.
Operating Instructions 07/2016 89

Table of Contents

Other manuals for Siemens SIMOTICS M-1PH8

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTICS M-1PH8 and is the answer not in the manual?

Siemens SIMOTICS M-1PH8 Specifications

General IconGeneral
BrandSiemens
ModelSIMOTICS M-1PH8
CategoryEngine
LanguageEnglish

Related product manuals