Interfaces
4.2 DRIVE CLiQ interfaces
PIN Signal name Signal type Meaning
5 NC Reserved, do not use
6 RXN I Receive data -
7 NC Reserved, do not use
8 NC Reserved, do not use
A + (24 V) VO Voltage supply for
DRIVE CLiQ, 450 mA
maximum
B M (0 V) VO Ground to 24 V
Signal type: I = Input; O = Output; VO = Voltage Output
Position of connectors
B
A
8
1
Figure 4-1 DRIVE CLiQ interface
4.2.2 Use of DRIVE CLiQ interface
Use of DRIVE-CLiQ
The DRIVE CLiQ interfaces are used to connect the components assigned to the control unit
in the drive assembly (e.g., active line module, motor modules, terminal modules, and sensor
modules from the SINAMICS family).
DRIVE CLiQ has the following properties:
• Independent expansion of components possible
• Automatic detection of components by the control unit
• Standardized interfaces to all components
• Uniform diagnostics down to the components
• Complete service down to the components
D4xx
Manual, 12.2004, 6AU1900-1AJ32-0BA0
4-3