Descriptions of functions
10.4 Communication via PROFIBUS DP
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
469
Links and taps
The links configured in the subscriber (connections to publisher) contain the following
information:
From which publisher is the input data received?
What is the content of the input data?
Where are the additional setpoints received?
Several taps are possible within a link. Several input data or input data areas, which are not
associated with one another, can be used as setpoint via a tap.
Links are possible on the drive unit itself. This internal link corresponds, as far as the timing
is concerned, to a link via PROFIBUS.
Requirements
The following requirements should be observed for the "direct data exchange" function:
STARTER as of Version 4.2
Configuration:
Drive ES Basic, Drive ES SIMATIC or Drive ES PCS7 as of Version 5.3 SP3
Alternatively using a GSD file
Firmware as of Version 1.2
The maximum number of process data per drive can be identified from the value in r2050
minus the resources that have already been used
A maximum of 16 links to publishers
Applications
For example, the following applications can be implemented using the "direct data
exchange" function:
Axis couplings