7
EN
ATYSt - 541995C - SOCOMEC
2. INTRODUCTION
ATySt “Automatic Transfer Switching Equipment” (ATSE) is designed for use in power systems for the safe transfer of a load
supply between a normal and an alternate source. The changeover is done in open transition and with minimum supply
interruption during transfer ensuring full compliance with IEC 60947-6-1, GB 14048-11 and other international TSE standards
as listed.
The ATySt is a full load break (switch type) derived transfer switching equipment where the main components are proven
technology devices also fullling requirements in IEC 60947-3 standards.
As a Class PC ATSE, the ATySt is capable of “making and withstanding short circuit currents” assigned to IEC 60947-3
utilization categories of up to AC23A, GB 14048-11, IEC 60947-6-1 and equivalent standards with utilization categories of up
to AC33B.
ATyStmotorisedsourcechangeoverswitchesensure:
• Power Control and Safety between a normal and an alternate source.
• A complete product delivered as a fully assembled and tested solution.
• Intuitive HMI for emergency / local operation.
• Integrated and robust switch disconnection.
• Window with clearly visible position indication I – 0 - II.
• An inherent failsafe mechanical interlock.
• Stable positions (I – 0 – II) non affected by typical vibration and shocks.
• Constant pressure on the contacts non effected by network voltage.
• Energy Efcient with virtually no consumption whilst on the normal, alternate or off positions.
• Quick, easy and safe dual “on-load” emergency manual operation.
(Manual operation is functional with and without the motorization in place).
• Extremely rugged, error free and built in padlocking facility.
• Straight forward installation with effective ergonomics.
• Minimal downtime with the possibility to perform easy maintenance.
• Simple and secure motorization controls interface with remote control.
• Straightforward ATS conguration for easy and fast commissioning.
• Integrated switch position auxiliary contacts.
• Dual active “product availability” status feedback for motorisation and ATS controllers.
• Ample accessories to suit specic requirements.
• Fully integrated ATS controller specically designed for Mains / Genset Applications.
• Power supply continuity for most network (transformer) applications...
Mains / Mains
D10
Automatic transfert Switch
LOAD
ATyS t