E6581697
E-15
5
+ The inverter was factory-configured by default so that if both forward and reverse run signals from
terminal board are ON simultaneously, the motor will decelerate to stop.
However, you can use the parameter  to select deceleration stop or reverse run.
5.9 Maximum frequency
: Maximum frequency
Function
1) Programs the range of frequencies output by the inverter (maximum output values).
2) This frequency is used as the reference for acceleration/deceleration time.
Output frequency
(Hz)
When 
=80Hz
When =60Hz
80Hz
60Hz
0 100% Frequency setting signal (%)
This function determines the value
in line with the ratings of the motor
and load.
Maximum frequency cannot be
adjusted during operation.To
adjust, first stop the inverter.
+ If  is increased, adjust the upper limit frequency  as necessary.
[Parameter setting]
Title Function Adjustment range Default setting

Maximum frequency 30.0-500.0 (Hz) 80.0

Table of Contents

Other manuals for Toshiba TOSVERT VF-MB1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-MB1 and is the answer not in the manual?

Toshiba TOSVERT VF-MB1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-MB1
CategoryInverter
LanguageEnglish

Related product manuals