6.33.5 Open network option
c000 to c119 : Communication option common parameters
c150 to c199 : ProfiBus DP option parameters
c200 to c249 : DeviceNet option parameters
c400 to c449 : EtherCAT option parameters
c500 to c549 : EtherNet common parameters
c550 to c599 : EtherNet/IP option parameters
c600 to c649 : Modbus TCP option parameters
c850 to c899 : EtherCAT option parameters
c900 to c909 : Communication option common parameters
+ ProfiBus DP option (Type: PDP003Z)
DeviceNet option (Type: DEV003Z)
EtherNet / IP-Modbus TCP option (Type: IPE002Z)
EtherCAT option (Type: IPE003Z)
Refer to each Instruction Manual of option for details.
6.34 Permanent magnet motors
f910 : Step-out detection current level
f911 : Step-out detection time
f912 : q-axis inductance
f913 : d-axis inductance
ï‚· Function
If the permanent magnet motor (PM motor) steps out and if the exciting current increases (it increases
in such a case) and remains above the value set with
f910 for the period of time set with f911,
the inverter will judge the motor to be stepping out and trip it. At that time, the trip message
"
sout" is displayed.

Table of Contents

Other manuals for Toshiba TOSVERT VF-MB1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-MB1 and is the answer not in the manual?

Toshiba TOSVERT VF-MB1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-MB1
CategoryInverter
LanguageEnglish

Related product manuals