E6581697
F-22
6
Starting frequency 
Output frequency (Hz)
0
Operation signal (F-CC)
Time
ON
OFF
6.7 Operation frequency
6.7.1 Starting frequency
f240 : Starting frequency
Function
The frequency set with
 is put out as soon as operation is started.
Use the
 parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3.0Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
[Parameter setting]
Title Function Adjustment range Default setting
f240 Starting frequency 0.1-10.0 (Hz) 0.5

Table of Contents