A-22
1
Remedies:
1. Use a meter output terminal in the inverter control circuit.
The load current can be output on the meter output terminal (FM). If the meter is connected, use an
ammeter of 1mAdc full scale or a voltmeter of 10V full scale.
0-20mAdc (4-20mAdc) can be also output. (Refer to section 3.4)
2. Use the monitor functions built into the inverter.
Use the monitor functions on the panel built into the inverter to check current values. (Refer to
section 8.2.1)
1.4.4 Installation
 Installation environment
This inverter is an electronic control instrument. Take full consideration to installing it in the proper operating
environment.
Warning
Prohibited
ď‚· Do not place any inflammable substances near the inverter.
If an accident occurs in which flame is emitted, this could lead to fire.
ď‚· Do not install in any location where the inverter could come into contact with water or other fluids.
This can result in electric shock or fire.
Mandatory
action
ď‚· Operate under the environmental conditions prescribed in the instruction manual.
Operations under any other conditions may result in malfunction.
Caution
Prohibited
ď‚· Do not install the inverter in any location subject to large amounts of vibration.
This could cause the unit to fall, resulting in bodily injury.

Table of Contents

Other manuals for Toshiba TOSVERT VF-MB1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-MB1 and is the answer not in the manual?

Toshiba TOSVERT VF-MB1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-MB1
CategoryInverter
LanguageEnglish

Related product manuals