Cooling unit Inputs available
Liebert® DS Water/Glycol Cooling
0
Models without high pressure transducers may have 2.
Liebert® PDX™ Air-Cooled
3
1 is used for low pressure transducers.
Liebert® PDX Water/Glycol Cooled
2
1 is used for a low pressure transducer. Optionally, a second for a high pressure
transducer.
Table 12.5 Number of Analog Inputs Available by Cooling Unit Type (continued)
13.5 Installing the Unit to Unit Network
13.5.1 Required Network Equipment
Ethernet cable CAT5 or greater
Maximum cable length is 328ft (100m).
An Ethernet repeater is required for cable lengths greaterthan328ft(100m).
Network switch
IEEE 802.3; IEEE 802.3u
10/100Mbps speed
Multiple 10/100 RJ-45 ports, one shared.
RJ-45 up link port
NOTE: Up to 32 cooling units may be connected in a unit to unit (U2U) network.
13.5.2 Planning Wiring Runs
When planning the layout of the conditioned space, consider the following:
Good wiring practices.
An Ethernet repeater is required for cable lengths greaterthan328ft(100m).
A private network that only connects and manages the cooling units is required.
Keep control and communication cables away from power cables to prevent electromagnetic interference.
Keep cables away from noise introducing device such as machines, fluorescent lights and electronics.
Do not bend cables to less than four times the diameter of the diameter of the cable.
Do not deform cables when hanging or securing in bundles.
Do not exceed 25lb (11kg) of tension when pulling cables to avoid stretching.
Do not damage cables when securing them. Use only approve hangers, such as telephone wire/RG-6 coaxial-
wire hangers.
Vertiv™ | Liebert® iCOM™Installer/User Guide
126

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert iCOM DP400/500 and is the answer not in the manual?

Vertiv Liebert iCOM DP400/500 Specifications

General IconGeneral
BrandVertiv
ModelLiebert iCOM DP400/500
CategoryThermostat
LanguageEnglish