EasyManuals Logo

Vertiv Liebert iCOM DP400/500 User Manual

Vertiv Liebert iCOM DP400/500
180 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #73 background image
Cascaded Units Off Delay
Length of time, in minutes, to delay powering-off a cascaded unit after fan speed drops below the Stop
Next Unit @
SYS Fanspeed setting.
Cascaded Units Quick Start
After a power cycle of the master unit, identical to Cascaded Units Delay except that it should be shorter to get units
to start more quickly after a power cycle.
This delay remains in effect until all cascaded units have been restarted, then the delay reverts to setting of
Cascaded Units Delay.
Max. Intermediate System Speed
Limits the fan speed of the group until all units in cascade are powered on. Once all units are operating, the fan speed
may increase beyond this setting.
Number of Connected Units
Number of units connected in the group if U2U networked.
Start Next Unit at SYS Fanspeed
Fan speed at which the next cascaded unit is powered-on.
Stop Next Unit at SYS Fanspeed
Fan speed at which the next cascaded unit is powered-off. Unit power-off may be delayed by Cascaded Units Off
Delay.
Based On
Select the way the sensor readings from each cooling-unit in the group are used to control temperature and humidity.
Options are:
Maximum: Based on the highest reading from a sensor in the group.
Average: Based on the average readings from the sensors in the group.
Type
Teamwork mode to use for the group.
6.2.2 No TeamworkMultiple Zones in One Room
When a teamwork mode is not used, cooling units work independently based on their own sensors. Standby and unit rotation
may be used, but cascading cannot.
6 Teamwork, Standby and RotationforCoolingUnits
65

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert iCOM DP400/500 and is the answer not in the manual?

Vertiv Liebert iCOM DP400/500 Specifications

General IconGeneral
BrandVertiv
ModelLiebert iCOM DP400/500
CategoryThermostat
LanguageEnglish