4.5.1 Setting Up Customer Input Events
Input devices must be wired to Terminal 24 through a dry contact to locations 50, 51, 55 and 56 for alarms 1 through 4
respectively, (For the terminal location, refer to the cooling unit electrical schematic and installation manual). Table 4.5
below, maps the customer input to the RADs
Customer Input Customer Input Terminal RAD Number RAD Terminal
1 24 1 50
2 24 2 51
3 24 3 55
4 24 4 56
Table 4.5 Customer Input Terminals to RAD Terminals
1. Touch , then > Alarm/Event Setup > Remote Alarm Device Input. The EDIT panel opens.
2. In Customer Input X (where X is the input number), select the input type that best describes the wired
device/input, see Table 4.6 on the next page.
3. In Customer Input X Active When, select whether the input is active (triggers events) when Opened or Closed.
4. Once input(s) are set, touch Save.
The customer-input settings are saved.
Customer Input Options
Customer Input X
Selects the customer wired input, where X is the input number. See Table 4.6 on the next page, for a description of
available values.
Customer Input
X
Active When
Selects when the input triggers an event. Options are:
• Opened: Events are triggered when the contacts across the corresponding RAD terminal strip are open.
• Closed: Events are triggered when the contacts across the corresponding RAD terminal strip are closed.