5.2.3 Troubleshooting Network Settings Issues
At the bottom of the U2U NETWORK SETTINGS panel, an Issues button indicates whether or not there are problems with the
network settings. The button indicates the number of issues and changes color when a problem exists, see Table 5.1 below.
Color Description
Green No problems. Number of issues is zero.
Red Problem(s) detected. Number of issues displays.
Table 5.1 Issues Button Status Colors
To view network issues:
1. When an issue is indicated, touch the Issues(s) button on the U2U NETWORK SETTINGS panel.
The ISSUES dialog opens.
2. Note the problems and Close the dialog, then address the issue:
• Touch the setting to correct.
The on-screen keyboard opens.
• Make adjustments and touch Go.
• Continue making corrections until no problems are indicated.
3. Verify that unit-to-unit communication is established, then touch Save.
NOTE: Depending on the changes made, the Save button updates to indicate the components that need rebooted or
restarted. If the control board reboots, the cooling unit suspends operation for 60 seconds, then resumes operating.
5.2.4 Modifying U2U Network Settings
1. Touch , then > BMS & Teamwork Setup > U2U Setup.
The U2U NETWORK SETTINGS panel opens.
2. Touch the setting to edit and make adjustments, then touch .
3. Verify that unit to unit communication is established, then touch Save.
NOTE: Depending on the changes made, the Save button updates to indicate the components that need rebooted or
restarted. If the control board reboots, the cooling unit suspends operation for 60 seconds, then resumes operating.
5 Unit to Unit Networking
61