3.2.2 Scheduling Condenser Fan Reversal
Condenser fan reversal schedules a reversal of the condenser fans, reversing air flow to help remove dust, paper, leaves and
such from the suction side of the condenser coil.
1. Touch , then > Scheduler > Condenser Fan Reversal Schedule. The TASK PROPERTIES panel
opens.
2. Adjust the schedule settings, and touch Save. The schedule is set up.
Touch Cancel to discard the changes.
Condenser Fan Reversal Task Properties Options
Reverse Fans At Duration
Length of time, in seconds, the fans are reversed.
Reverse Fans Every
Selects number of days between fan reversal.
Reverse Fans Now
Enables/Disables immediate fan reversal.
3.2.3 Scheduling Sleep Times for Thermal Management Units
Unit sleep schedules turn off units during low demand as long as return temperature remains below the alarm threshold.
1. Touch , then > Scheduler > Unit Sleep Schedule. The TASK PROPERTIES panel opens.
2. Adjust the schedule settings, and touch Save. The schedule is set up.
Touch Cancel to discard the changes.
Unit Sleep Schedule Task Properties Options
Interval 1/2
Start and finish time of day that sleep mode operates.
Interval Day
Selects days on which sleep mode operates for the intervals specified in Interval 1 and Interval 2.
Sleep Mode
Enable/disable sleep schedule. When checked, the schedule is run. When not checked, the scheduling parameters are
ignored.
3 Service Operation
33

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert iCOM DP400/500 and is the answer not in the manual?

Vertiv Liebert iCOM DP400/500 Specifications

General IconGeneral
BrandVertiv
ModelLiebert iCOM DP400/500
CategoryThermostat
LanguageEnglish