Event Description
PB1 OUT PRES
SEN FAIL
Outlet refrigerant-pressure-sensor failure. Pump shut down.
Event is reset when condition clears.
PB1 OUT TEMP
SEN FAIL
Outlet refrigerant-temperature-sensor failure. Pump shut down.
Event is reset when condition clears.
PB1 CAN
DISCONNECTED
iCOM lost CAN communications with pump board. Pump shut down.
Event is reset when condition clears.
PB1 REMOTE
SHUTDWN
Remote shut-down requested. Pump shut down.
Event is reset when condition clears.
PB1 STARTUP
FAIL
Three pump start up attempts in a row have failed.
Event must be reset manually.
PB2 BOARD
FAIL
An unrecoverable failure of the pump control board occurred. Pump shut down.
Reboot pump board to reset event.
PB2 CAVITATE
SHUTDOWN
Pump has cavitated and shut down.
Event is reset when iCOM requests a new startup.
PB2 IN PRES
SENS FAIL
Inlet refrigerant-pressure-sensor failure. Pump shut down.
Event is reset when condition clears.
PB2 IN TEMP
SENS FAIL
Inlet refrigerant-temperature-sensor failure. Pump shut down.
Event is reset when condition clears.
PB2 INV DATA
SHUTDOWN
Invalid data detected and pump shut down.
Event is reset when iCOM requests a new startup.
PB2 LO DIFF
PRESSURE
Pump differential pressure fell below a lower threshold and pump shut down.
Event is reset when iCOM requests a new startup.
PB2 LO OUTLET
TEMP
Pump outlet refrigerant temperature fell below a lower threshold and pump shut down.
Event is reset when iCOM requests a new startup.
PB2 OUT PRES
SEN FAIL
Outlet refrigerant pressure sensor failure. Pump shut down.
Event is reset when condition clears.
PB2 OUT TEMP
SEN FAIL
Outlet refrigerant-temperature sensor failure. Pump shut down.
Event is reset when condition clears.
PB2 CAN
DISCONNECTED
iCOM lost CAN communication with pump board. Pump shut down.
Event is reset when condition clears.
PB2 REMOTE
SHUTDWN
Remote shut-down requested. Pump shut down.
Event is reset when condition clears.
PB2 STARTUP
FAIL
Three pump start-up attempts in a row have failed.
Event must be reset manually.
Table 4.4 Events Specific to Liebert EconoPhase (continued)
4 Managing Events: Alarms,WarningsandMessages
51