9 Electrical Installation
YASKAWA TOEPC71061723A YASKAWA AC Drive CR700 Quick Start Guide 43
Table 9.4 Multi-function Digital Input Terminals
Mode Terminals Name (Default)
Function (Signal Level)
Digital
Inputs
S1
Multi-function input selection 1
(ON: Forward run OFF: Stop)
• Photocoupler
• 24 V, 6 mA
Note:
Install the wire jumpers between terminals SC-SP and SC-SN to set the MFDI power supply.
• SINK Mode: Install a jumper between terminals SC and SP.
Do not short circuit terminals SC and SN. Failure to obey will cause damage to the drive.
• SOURCE Mode: Install a jumper between terminals SC and SN.
Do not short circuit terminals SC and SP. Failure to obey will cause damage to the drive.
• External power supply: No jumper necessary between terminals SC-SN and terminals SC-SP.
S2
Multi-function input selection 2
(ON: Reverse run OFF: Stop)
S3
Multi-function input selection 3
(External fault (N.O.))
S4
Multi-function input selection 4
(Fault reset)
S5
Multi-function input selection 5
Brake Release Check
S6
Multi-function input selection 6
(Multi-step speed reference 1)
S7
Multi-function input selection 7
(Multi-step speed reference 2)
S8
Multi-function input selection 8
Baseblock Command (N.C.)
S9
Multi-function input selection 9
(Through Mode)
S10
Multi-function input selection 10
(Through Mode)
SN Multi-function input power supply 0 V
MFDI power supply and sensor power supply, 24 Vdc (max. 150 mA)
Note:
Do not short circuit terminals SP and SN. Failure to obey will cause damage to the drive.
SC
Multi-function input selection common
SP Multi-function input power supply +24 Vdc
Safe Disable
Input
H1 Safe Disable input 1
Remove the jumper between terminals H1-HC and H2-HC when using the Safe Disable input.
• 24 V, 6 mA
• ON: Normal operation
• OFF: Coasting motor
• Internal impedance 4.7 kΩ
• OFF time of at least 2 ms
H2 Safe Disable input 2
HC Safe Disable function common
Master
Frequency
Reference
+V Power supply for frequency setting 10.5 Vdc (allowable current 20 mA max.)
-V Power supply for frequency setting -10.5 Vdc (allowable current 20 mA max.)
A1
Multi-function analog input 1
(Master frequency reference)
Voltage input
Select the signal level with H3-01 [Terminal A1 Signal Level Select].
• -10 V to +10 V/-100% to +100% (input impedance: 20 kΩ)
• 0 V to 10 V/100% (input impedance: 20 kΩ)
A2
Multi-function analog input 2
(Combined to terminal A1)
Voltage input or current input
Select the signal level with DIP switch S1 and H3-09 [Terminal A2 Signal Level Select].
• -10 V to +10 V/-100% to +100% (input impedance: 20 kΩ)
• 0 V to 10 V/100% (input impedance: 20 kΩ)
• 4 mA to 20 mA/100%, 0 mA to 20 mA/100% (input impedance: 250 Ω)
A3
Multi-function analog input 3/PTC input
(Auxiliary frequency reference)
Voltage input
Select the signal level with H3-05 [Terminal A3 Signal Level Select].
• -10 V to +10 V/-100% to +100% (input impedance: 20 kΩ)
• 0 V to 10 V/100% (input impedance: 20 kΩ)
PTC input (Motor Overheat Protection)
Set DIP switch S4 to “PTC” to set terminal A3 for PTC input.
AC Frequency reference common 0 V
E (G) Shielded cable -
■ Output Terminals
Refer to Table 9.5 and Table 9.6 for a list of output terminals and functions.
Text in parenthesis indicates the default setting for each multi-function output.