SECTION 1 - OVERVIEW
Form 11
Prior to shipping, the unit is completely assembled at
the factory. Interconnecting piping is assembled and
the complete unit is wired and leak-tested.
The chiller is split down the middle and shipped in two
assemblies:
1. The condenser-side assembly.
2. The evaporator-side assembly.
3. Refrigerant charges are included.
4. Miscellaneous shipped loose items.
Arrangements with the local service office must be
made to ensure refrigerant is on-site when the unit is
ready to be charged.
Condenser-Side Assembly (Condenser /
OptiView™ Control Center / Variable Speed
Drive)
The Condenser-side assembly consists of the Condens-
er, the OptiView™ Control Center and the Variable
Speed Drive.
• All conduit is left on the condenser shell.
• Interconnecting piping between shells are anged
and capped, requiring no welding.
• All openings on the condenser shell are closed
and shipped charged with a 3 to 7 PSIG (20 to 50
kPa) holding charge of dry nitrogen.
Evaporator-Side Assembly (Evaporator /
Driveline / Power Panel)
The evaporator-side assembly consists of the evapo-
rator, the driveline (compressor/motor assembly), and
the Power Panel.
• All conduit is left on the evaporator shell.
• Interconnecting piping between shells are anged
and capped, requiring no welding.
• All integral wiring is left on the compressor.
• All openings on the evaporator shell and driveline
are closed and shipped charged with a 3 to 5 PSIG
(20 to 50 kPa) holding charge of dry nitrogen.
Miscellaneous Material
The following items are shipped together:
• Four (4) vibration isolation pads (or optional
spring isolators and brackets)
• Other shipped loose items, including piping, wa-
ter temperature controls, wiring, etc.
• VSD operating coolant (inhibited water)