Parameters 151
Supervision 4 Bit 3 of 32.01 Supervision status.27
Supervision 5 Bit 4 of 32.01 Supervision status.28
Supervision 6 Bit 5 of 32.01 Supervision status.29
Other [bit] Source selection (see Terms and abbreviations). -
20.26 Jogging 1 start source If enabled by parameter 20.25 Jogging enable, selects the
source for the activation of jogging function 1. (Jogging
function 1 can also be activated through fieldbus
regardless of parameter 20.25.)
1 = Jogging 1 active.
Notes:
Jogging is supported in vector control mode only.
If both jogging 1 and 2 are activated, the one that was
activated first has priority.
This parameter cannot be changed while the drive is
running.
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
Supervision 1 Bit 0 of 32.01 Supervision status.24
Supervision 2 Bit 1 of 32.01 Supervision status.25
Supervision 3 Bit 2 of 32.01 Supervision status.26
Supervision 4 Bit 3 of 32.01 Supervision status.27
Supervision 5 Bit 4 of 32.01 Supervision status.28
Supervision 6 Bit 5 of 32.01 Supervision status.29
Other [bit] Source selection (see Terms and abbreviations). -
20.27 Jogging 2 start source If enabled by parameter 20.25 Jogging enable, selects the
source for the activation of jogging function 2. (Jogging
function 2 can also be activated through fieldbus
regardless of parameter 20.25.)
1 = Jogging 2 active.
For the selections, see parameter 20.26 Jogging 1 start
source.
Notes:
Jogging is supported in vector control mode only.
If both jogging 1 and 2 are activated, the one that was
activated first has priority.
This parameter cannot be changed while the drive is
running.
For the selections, see parameter 20.26 Jogging 1 start
source.
Not selected
20.30 Enable signals
warning function
Selects the enable signal warnings that will be
suppressed. This parameter can be used to prevent these
warnings from being added to the event log. Whenever a
bit of this parameter is set to 1, the corresponding warning
is suppressed.
0000h
No. Name/Value Description Default
FbEq 16
ACS180 FW.book Page 151 Tuesday, March 9, 2021 2:25 PM

Table of Contents

Other manuals for ABB ACS180

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS180 and is the answer not in the manual?

ABB ACS180 Specifications

General IconGeneral
Product TypeDC Drive
Number of Phases1 or 3
IP RatingIP20
Communication InterfacesModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-40 to +70 °C
Relative Humidity5 to 95 % non-condensing
AltitudeUp to 1000 m