Practical examples 107
Downloading the diagnostics of APBU branching unit
APBUDL is a tool program for APBU datalogger control and data upload. It is highly
recommended to use the APBUDL program with the RUSB-01 adapter. With following
instructions the datalogger file is downloaded for further analysis.
Program file is APBUDL.exe. These files are also needed in the same directory or in the
system directory: Dwc_ddcp.dll, amctvb.dll, amctooli.dll.
Status:
No communication (No communication between PC and APBU board)
APBU found (Communication OK, logic version of APBU board)
Status (Status of loggers; if data collection is on: logging. If logger has triggered: data
ready)
Commands:
u = Upload a logger
t = Trig user logger
l = Start user logger
q = Quit
Data upload:
u = Upload a logger
Define how many percent of the samples is uploaded (1…100)
Define which logger is uploaded (F/L/U) [First/Last/User]
Following files will be created:
First Logger: first.csv
Last Logger: last.csv
User Logger: user.csv
Note: Files must be renamed.